bs7671 cable derating factors
Cable Sizing - derating factors - Wiring and the Regulations BS 7671 - IET EngX - IET EngX This site uses cookies. The physics involved with heat loss have similarities with those of mechanical engineering and are based on heat transfer principles. If the appropriate correction factors are applied, the results will be the same. Discover how this hybrid manufacturing process enables on-demand mold fabrication to quickly produce small batches of thermoplastic parts. The conductor must be derated according to NEC table 310-16 because the ambient temperature exceeds 30 C. Video of the Day Step 2 Table 4: Cable surrounded by thermal insulation length in insulation mm derating factor 50 0.89 100 0.81 200 0.68 The reports are still available and can be purchased here. 0000007414 00000 n Cloud based - any device, anywhere. Using the factors noted earlier: 285 A x 0.80 x 0.88 = 201 A. 0000006009 00000 n More than six cables grouped together require a de-rating factor of 0.85. Soil resistivity is affected by many factors including geographic location, soil composition and water flow and it will also change seasonally. Although the document is a British Standard, it is also known as (and jointly labelled as) the IEE Wiring Dose bicc comply? The references in the document indicate that it was produced in the late 1940s or early 1950s. 0000005800 00000 n Close this window and log in. We're about to take you to the IET registration website. If every possible cable and installation method was identified in BS 7671:2018+A1:2020, the size of the Standard would increase significantly. Appendix 4 of item 7.1 reference method D states if the specific installation parameters are known (thermal resistance of the ground, ground ambient temperature, cable depth), reference can be made to the cable manufacturer or the ERA 69-30 series of publications, which may result in a smaller cable size being selected. as seen in Figure 5. well, it should be treated as two adjacent cables carrying the same current, and grouped, just the same as you would (I hope) for a hairpin of cables going up and down the wall to call in at a switch for a heater or similar on a radial as well. The values used for calculation will depend on the actual ground conditions and material used for backfilling. Had the derating factors for conduit fill and ambient not been required, a 3/0 copper conductor would have met the needs for this application. Rating Factor for cables in buried ducts Rating Factors for direct buried cables NOTE 1: The rating /:lcIOl"S given haw bet:n avenlgec! 0000006711 00000 n Z Extra holes not really required unless the parallel length of touching cables in the joist was so long that no significant heat conducted along the cable, and the fit so tight that no air could move between them - so perhaps a very thick joist like a ship's timber, but not the average bit of 2*8 or 3*10 - (even less of a concern in the 'engineered joists' that are an I beam of 2 bits of what looks like roof batten attached to a strip of plywood)If in doubt a slight slotting in the direction of the grain is enough to open up an air path, though to be honest T &E being flat, in a round hole, I'd not worry.Because the heat generated (and in the simple systems the temperature rise ) is proportional to the square of current you may find do not need to de-rate so much - 70% of the current in 2 cables is the same total heating as 100% of the heat in one cable (as 1.4 is sqrt of 2), but of course the surface area to sweat it out over is increased over the single cable case (but not quite doubled as the sides in contact are unable to lose heat in the way they would be if there was a gap between the cables) Also flat cables touching on the thin edge cool better than touching on the broadside - but this sort of thing rapidly becomes subject to too many subtle effects to be safely captured in a simple set of rules.However a round bundle of cables is the worst case, for the one in the middle, and keeps getting worse the more cables are added, while if you can lay your cables side by side, then only the nearest few neighbours to any given cable have much effect, and the effect on the grouping factor is that for more than a few cables the change in cg of adding another cable is small - the greatest steps are between 1 and 2 and then 2 and 3 cables, and a flat lay of 4 cables is almost the same as a flat lay of 40.Mikeregards,Mike. For further information, see the IET Wiring Matters article Amps per pound. CEC Designer Veli has nearly two decades of experience in the renewable industry. 0000002031 00000 n For example, Table 310.15 (C) (1) requires a THWN No.4 copper conductor, normally valued at 85 amps according to Table 310.16, to be derated to 80% of its value when there are 4-6 current-carrying conductors bundled together. Rating factor for grouping of cables = 0.61 (Appendix 1.4) (Assumed 6 cables 150mm spacing formation) Overall admissible ampacity correction factor = 0.82 x 0.73 x 0.92 x 0.61 = 0.336 1.2. If a detailed heat transfer calculation is carried out, however, a more accurate analysis of the whole cable route can be performed. Low voltage cable derating factors -Australian and New Zealand conditions The current rating of a cable is affected by the presence of certain external influences. xdq%_OL`-6G%ZHz`C There are other considerations to be taken into account by the electrical designer when selecting a suitable CSA of cable, such as length, voltage drop, energy let through (I2t) from the protective device and thus the energy withstand rating of the cable. Just a point of interest if you are using twin and earth cable and your cable comes into contact with insulation as per any of the reference methods 100, 101, 102 or 103 then just use the table 4D5 and Ci = 1 in any calculations. IEC 60502 is an International Electrotechnical Commission standard, which gives current ratings for medium voltage cables. If the main load is half way round, that's the whole lot in two adjacent cables. of Cables) 16 x 18.0 (Factor for 4mm cable) = 289.6 Total Cable Factor = 1239.6 Standard Trunking Cable Factors Standard Trunking Capacity Factors Show entries Search: Re: Cable Size for 7.5 KW motor 03/29/2010 1:30 AM By applying derating factor as 0.7 to 0.75 to 3Cx4Sq.mm, u may . 0000085335 00000 n Whilst BS 7671:2018+A1:2020 is extremely useful as a guide for determining the current-carrying capacity of cables for most electrical installations, there are situations when a detailed current-carrying capacity calculation might be required. Don't worry though, you'll be sent straight back to the community after completing the registration. Finite element analysis is a numerical method used to solve complex engineering problems, usually carried out on simulation software. Traditionally, tabulated values were not provided in the IEE Wiring Regulations, the current-carrying capacity ratings for cables buried directly in the soil first appeared in the 13th Edition of the IEE Wiring Regulations in 1955 as seen in Figure 2. Cable Derating (Factors) Cable Sizing Input Data Checklist. Cable Sizing Standards. stream *Eng-Tips's functionality depends on members receiving e-mail. The calculation of cable rating follow t he derating factor method, see Cable Derating (Factors) . When multiple cables are in proximity, each contributes heat to the others and diminishes the amount of external cooling affecting the individual cable conductors. endstream endobj 149 0 obj <. ~~~/?Ppx.F@ 0K^,spyi>}>o?g'{wo?nO?~~oLG`|0_N~m#dGg?6?w7ovv_ ~v`C#t%(7cP>$7=^JJKh$eewE1l?lnrOB%@?6x8u"51SbeHD4_/Ba_=}$A5(scQw|Az7cnw; Uk{j3$;g/?uQ o8qbE>9D)q~0;Uch%omWg}ckRXe@.HpWwB<=s6K>;^vK#2!6l,C T1 Pvf Cable current carrying capacity. The ERA series of reports are still available and can be purchased from the RINA website. DE-RATING FACTORS Our Company Genesis & Evolution Why Us KEI Power Gallery Beyond Business Certifications Downloads Clients Testimonials Reach Us Locate Us CALL (112) 681-8840 Follow Follow Toggle navigation Products & Solutions Extra High Voltage Cables High Voltage Cables Low Voltage Cables Control Cables House Wire HomeCab-FR BanFire-ZHFR Some studies have found the empirical method to be conservative, owing to the fact that it does not take account of the specific thermal environment outside of the cable. Do you need to include all cables fixed to a cable tray when calculating grouping factors. 5;b^VL477/8:m}*lXIw{%;YOol*V5@r,;VkYNM|&Q@VVGC`i(c cB&0s!|8~%q$sJ(2% cL*qOX_Q>H+i.3@qhJ Firstly how much current is your appliance going to use? 0000015597 00000 n To avoid the ordeal of calculating the current-carrying capacity of cables, where possible, utilise the installation methods and rating factors already published: someone has already done the hard work for you! APPENDIX 1: Correction Factors for Sizing of Cable Conductors (1) Correction factors for ambient temperature Table 1: Correction factors for ambient temperature Note: Ths table applies where the associated overcurrent protective device is intended to provide shor circuit protection only. Determination of the current-carrying capacity by calculating the actual heat transfer is likely to result in a less conservatively sized cable. In this electricians Q&A, Joe Robinson takes a deep dive into ther. ERA 69-30. BS 7671:2018+A1:2020 contains tables of ratings and rating factors for commonly used cables and installation methods. British Cables Company introduces new cables to its range. lol!!! 0000010392 00000 n If the wire is rated to 150 0 C derate the values in the table by 80%, 70% for 135C wire, and 115% for 260 0 C. Equally loaded just means that that's what they've assumed when calculating the numbers in that table (i.e. 4 0 obj Created for free using WordPress and, Common Mode Voltages: Causes, Effects and Mitigation. <<95D84A24FD5A1F4C8152C1D91F51EC80>]>> 0000078628 00000 n Trying to create tables for other conditions rapidly gets very silly as there are just too many combinations of how things could be arranged (90% fully loaded, 10% half loaded; 50% full loaded, 25% half loaded, 10% 10% loaded 15% unloaded.)Where things aren't equally loaded then it's NOT saying you can ignore grouping - it's just saying that the figures in that particular table might not be entirely accurate - hinting that you might need to take other factors into consideration (i.e. Examine how the principles of DfAM upend many of the long-standing rules around manufacturability - allowing engineers and designers to place a parts function at the center of their design considerations. Selecting Copper, XLPE, 3*50+25 mm 2 , its current is 185 A, Derating this current 185 * 0.93 = 172 A. . Not every installation method is provided in BS 7671, as there are too many permutations. 0000001244 00000 n 2023 The Institution of Engineering and Technology, The Institution of Engineering and Technology is registered as a Charity in England and Wales (no 211014) and Scotland (no SC038698). Typically, electrical design software is used for cable selection on larger installations. CJX7b.zd@c41DV3+l[r~SKT? xZ[cs@k./0gqW5J$?Q /3=+uUW5mFN_zo++y.t^02:xr*ZK$7_Cw/~5a(vW~?jd64s/k=!W?fYZ`?x}h571t"TI?xf`D4i* k=VHYh$E#-Snf#9D?X 1?q9!Qkp"L$7+(dvirmlDMR[bvlz72Qbpqm>fs?8Y#f:S0SrTN:+IY+hY7wQ ot7bJ[!eN$KRv&%BiV,B[Zgbb+L5L o$+E0VY0B The assumed values for each publication are identified in Table 1 below, the main influencing factor is the soil thermal resistivity. I Accept Cookies For example ambient temperature (Ca), buried cables (Cc), Semi-enclosed fuse to BS3036 (Cf) etc (Take a look at Appendices 4 Section 3 of BS7671 for more rating factors that may apply). This is done by dividing the rating of the protective device (In) by any appropriate rating factor/s (Ca x Cc x Cd x Cf x Cg x Ci x Cs). I ended up having to run some lighting circuits in 2.5mm to negate them from grouping calc for the RFC circuits. P1{:f["ypc &@8o:a!`r BS7671 18 th Edition Cable Sizing Calculation Show 1 CABLE SIZING OR Doing it in Groups . Current capacity to BS 7671, ERA 69-30 and IEC 60502. Some electrical design software packages specifically refer to BICC cable data but other manufacturers data also exists, other software packages refer to ERA 69-30. According to the IEEE document Ampacity Calculations for Cables in Shallow Troughs (G. Anders, M. Coates and M. Chaaban), a draft document has been found that derives a simple equation for the calculation of thermal resistance of a trough. Lets say its a 5kW appliance and we are going to be using a 70 deg C thermoplastic flat sheathed cable. ambient temperatures > 30C. The nearest size of standard trunking with a capacity factor greater than 1239.6 is 75 x 50mm? Thermal resistivity of soil is different to soil resistance. Solar Radiation Effects. Derating: No derating is currently applied to the current ratings tables 310.15 (B) (16) and 310.15 (B) (17).. To ascertain that the current-carrying capacity of the circuit is sufficient factoring the presence of harmonics in the system, Table 4Aa (BS7671 - 2011) provides some factors in determining the cable sizes. Note: The minimum current carrying capacity stated herein does not include other derating factors such as grouping, temperature, etc. These standards contain methods for calculating the permissible current rating of cables from details of the permissible temperature rise, conductor resistance, losses and thermal resistivities, using analytical methods. In our example we have an ambient temperature of 35 deg C (Ca = 0.94 From Table 4B1) and some thermal insulation in a stud wall but with the cable touching the inner surface of the wall (aka reference method 102 in table 4D5). 0000001839 00000 n Later, in the reissued Fourteenth Edition of the IEE Wiring Regulations incorporating Amendments 1970, 1974 and 1976 including metric units, it was stated that current ratings shall be in accordance with ERA report 69-30 as seen below in Figure 4. These are related to the line voltage for three phase circuits and phase voltage for single phase circuits. xNf(@-c]D$t7:z)Q By the time tabulated values for buried cables were reintroduced in the Seventeenth Edition of the IEE Wiring Regulations in 2008, the IEE Wiring Regulations had become a British Standard, BS 7671:2008, based on the European CENELEC HD 60364 series of standards. However, for comm/ind they would apply the group ratings to the legs, depending on anticipated use/load. UTg-3[f;"v,u|==:vao~|?m{?=?;9#<=}?^7||o}=oOOKo~4o04qzt:o>oO{? We're about to take you to the IET registration website. 0000078301 00000 n It is assumed that the maximum ambient temperature is 30C and the maximum ground temperature id 20C. You have to look at using the <30% of the grouped rating for the cable i.e. The data shows both single wire and multi-conductor wire at 70 0 C in a vacuum (no air flow). 0 l^~u%_?2J?Xm1~0lQ3C7X ncF?' The rating for the bottom tray is the same as for a single tray, since the cables on the bottom tray do not know that other trays containing other cables are above them. 193 0 obj <>stream The derating factor accounts for the added thermal resistance present when a. Consider a 20/3.3 kV, 12.5 MVA transformer to be fed by direct buried, 3 core XLPE, SWA, PVC, copper conductor cable. presumably then each leg should also be run separately in floor joists - at the risk of making Swiss cheese out of the joists with all the cables run in separate holes, or upping the cable size based on rating factors. The question that was asked, and is primarily responsible for publishing this article, was: The enquiry was related to an extensive electric vehicle (EV) charging project: the designer needed to consider derating factors for up to 60 cables installed in a concrete trench. Cable sizing compiles with: - BS 7671, IEE Wiring Regulations Cable size is selected as follows: 1. Three criteria are given for cable selection: (a) Current-carrying capacity (b) Voltage drop (c) Short-circuit temperature rise This standard provides sustained current-carrying capacities and voltage drop values for those types of electrical cable and installation practices in common use in Australia. 0000001701 00000 n 0000009580 00000 n Knowing this we can select the size of the protective device (In) and in this instance we are going to use a 32A circuit breaker. *NOTE: The third harmonic content expressed as total harmonic distortion. Promoting, selling, recruiting, coursework and thesis posting is forbidden. 0000005725 00000 n Whilst BS 7671:2018+A1:2020 does cover most typical electrical installations, there will be instances when installations will differ from those identified in the Standard. Reference method D of BS 7671:2018+A1:2020 should be applied for cables buried in the ground in and around buildings. Unless specific details are known, the electrical designer should use the tabulated values provided in BS 7671:2018+A1:2020. Hzd}-/ *@. Derating factors should be applied to the cable current. This can produce an excessive amount of heat which in turn can damage the cable and the installation and may even cause a fire. startxref << /Length 5 0 R /Filter /FlateDecode >> 0000000016 00000 n Want to participate in the discussions? This ebook covers tips for creating and managing workflows, security best practices and protection of intellectual property, Cloud vs. on-premise software solutions, CAD file management, compliance, and more. Calculation of voltage drop uses tables of resistive and reactive voltage drop. stream Total derating factor = 0.89 * 1.05 * 1.0 = 0.93. Appendix 4 of BS 7671 by Mark Coles Appendix4,Current-carrying capacity and voltage drop for cables and flexible cords,hasseensignificant . Figure - 2 (reference fuse . What is the maximum number of cables that can be installed in a pre-formed concrete cable trough? capacity of the cable shall be reduced appropriately depending on the size of cable, length in Table 4 are appropriate to conductor size up to 10 mmsq in thermal insulation having a thermal conductivity greater than 0.0625 W/K.m. 0000071888 00000 n As far DC cable sizing in PV projects is concerned, PV engineers consider DC cable sizing based on cable derating factors such as - depth of cable laying, ground/air temperature, thermal resistivity of soil and grouping of cable that . Simultaneous Overload - can the other cables on the cable tray that are alongside your cable be subject to simultaneous overload?? BS 7671. So the design current (Ib) would be 5000/230 = 21.73 Amps. 2023 The Institution of Engineering and Technology. 148 0 obj <> endobj So if derating to 0.88 is required for number of cables, and derating to 0.93 is required for an upper tray, then the final figure is 0.88 multiplied by 0.93. 0000008621 00000 n Don't worry though, you'll be sent straight back to the community after completing the registration. Other losses include dielectric losses from insulating materials, skin effect introduced by alternating current, and eddy current losses. For example, suppose a cable had an ambient temperature derating factor of = and a grouping derating factor of =, then the overall derating factor = =. Reference method Exampleofinstallationmethod Relevanttablefrom BS7671:2008 Image. However, when the appropriate correction factors are applied, the results will be the similar as they are based on calculation methods derived from IEC 60287 Electric cables - Calculation of the current rating. Irnd`u3=](tdd= L8z[Wlm`= !paX}xZQ#)aC*UryS>P&O )X]B. F/T 183 issued by the ERA. vi}z7{?8x=l"t\F1'lnxN+h'qVs6GX1Cyx8N"/V*#JP%/~7d_}l?A#NLXh\h|gq$vtmO89dp|d{;>1-bSJb_" RT'C? Minimum Cable size REWIREABLE FUSES BS 3036 SEMI-ENCLOSED FUSE We'd also like to set optional analytics cookies to help us improve it. However, this is unlikely to be a cost-effective option for smaller CSA cables when compared with using a more conservative cable size. BS 7671:2018+A1:2020 provides tabulated current-carrying capacity values for common installation methods. Typically, cables installed in ducts will need to be larger than those buried direct in the ground as the air surrounding the cable is heated by thermal radiation from the cable, reducing heat dissipation. 1.5mm cable but circuit only loaded with a couple of amps. Copyright 1998-2023 engineering.com, Inc. All rights reserved.Unauthorized reproduction or linking forbidden without expressed written permission. Rosa Ponce. 0000085058 00000 n Part P vs BS7671, Why Electrical Installation Training Is Important, All About RCDs (residual current devices), Part 5: Selection and Erection of Equipment, Part 7: Special Installations or Locations. fpo&Q)"oHu4D3]*?/ 23,A o?NTpZ4H=`y53,O5+1-WC8Fy"n\IGOS`] pEA L1xi1g]lG+@/GCJ&$y91lIOJ8aSu|)w)ue(,'k5J%Z'#MD"%#B x 0000004990 00000 n Derating factors, given in BS7671, for cables in touching trefoil formation are appropriate for cables in quad bundles Voltage drops for circuits in quad formation should be calculated using the values tabulated in BS7671 for cables in flat touching formation BS 7671 is the UK requirements for electrical installations standard, also known as the Wiring Regulations. The derating factor is applied to reduce the cable's current carrying capacity. This applies to a cable in a partition where the construction includes metallic parts other than fixings irrespective of the depth of the cable. Fictitious Dimensions. Part III of the ERA 69-30 provides values of current-carrying capacity and calculation methods for, sustained current ratings for 600/1000 V and 1900/3300 V cables with 70C thermoplastic insulation (ac 50 Hz and dc). The values of current-carrying capacity tabulated in the report are in accordance with IEC 60287 Electric cables - Calculation of the current rating. Both the load factor and the RHO value of the backfill also play large roles in determining the potential derating of the conductors in the duct bank. Figure 4: extract from the Fourteenth Edition of the IEE Wiring Regulations 1966 incorporating Amendments 1970, 1974 and 1976. Step 1 Determine if the highest ambient temperature a conductor is subjected to exceeds 30 degrees Celsius. Got the answer from BS 7671, but still got another question on the previous attachment. Registration on or use of this site constitutes acceptance of our Privacy Policy. BICC or BS7671 comply for design Anthony Sullivan over 4 years ago Hello IET guys I have a problem where a cable installed on site doesn't comply to Bs7671 current carrying capacity for underground cable reference method D the engineer who design the cable used amtech and data from bicc with reference method 110. The resulted current should be the new current carrying capacity for the cable. Up to six cables can be bunched together without derating. 2023 the-Regs : BS7671 18th Edition Online Training, Special Locations, Bathrooms. Register; Login. If cables are buried in the ground, either direct or inside ducting, reference method D (Figure 1) is applicable and the appropriate value should be selected according to its type from the relevant table identified in Appendix 4. NOTE 3: In the case of a cable connector at least 25cm (10 inches) of the cable shall be . It is important that these calculations are carried out by someone who is experienced in this field of work (which may not necessarily be an electrical engineer). 0000009088 00000 n Cable derating ensures all factors which can increase the temperature experienced by the installation is properly accounted for when selecting cables to prevent damage to the cable insulation and reduce system losses. BS7671 Grouping Factors Mark Freeman over 1 year ago Hi, With reference to BS7671, in table 4C1 (Page 396) it states that: Where horizontal clearances between adjacent cables exceed twice their overall diameter, no rating factor need be applied. of Cables) 10 x 95 (Factor for 35mm cable) = 950 (No. If this is the case, seek advice from someone with experience of carrying out this type of calculation. Failing that, speaking to the manufacturers of the cable is always a good place to start. The thermal resistivity of soil refers to its ability to dissipate heat, which is relevant to the current-carrying capacity of cables. k2-3,Kw#`nu>+LKYgT BS 7671: Introduction and Overview A BS 7671: 2008 - Introduction and Overview A 1 Introduction to BS 7671: 2008 BS 7671: 2008 was published during January 2008 as a signi cant new Edition of this fundamental Standard. Even then couldn't group more than 4 power circuits. Thanks. Z+7`Mq!p#pg Py_!!G/[3A`.TOuL. I have attached a cable verification sheet made in Amtech software. 0000088434 00000 n Manufacturers provide data . BS7671:2018+A2:2022 Let's take a quick run through the new 18th Edition Wiring Regulations book, which includes Amendment 2 that was introduced in March 2022, BS7671:2018+A2:2022. 0000004403 00000 n 0000002616 00000 n These values were based on the conditions identified in the supplement to Report No. k = factor which is 143 for Copper cable (from IEC 60364-4-43). All relevant derating factors are applied. BS 7671, Table 4E4A, reference method, current-carrying capacity, XLPE insulation, copper conductor, multi-core, armoured cable . In the first example, a 4,000-amp duct bank with a design load of 3,600 amps is simulated based on an earth RHO factor of 90, dirt RHO factor of 90 and a load factor of 100 . This method subdivides the problem into smaller problems called finite elements which these are solved and put back into the original problem. The current-carrying capacity of a cable is determined by the maximum permitted conductor temperature and the rate at which it dissipates heat into the environment, taking into account the surrounding material, which will have thermal properties and resist the dissipation of heat, this is called I2R losses. 0000076607 00000 n BS 7671:2018+A1:2020 contains tables of ratings and rating factors for commonly used cables and installation methods.